8 Guage Stranded Romex (40' run). This installation will never work out in a positive way. I will check that tonight. Can you log the dimmer voltage as you run the hot water (causing the heater to come on)? B BillyMac59 Why is there cold water when flushing sediment from water heater? I would like to convert a 12v battery supply to AC voltage ranging anywhere between 140v to 240v to run LED tubes rated 22 W for 3 hours. From https://www.justanswer.com/ythi\rJustAnswer Customer: Tankless hot water heater flickering the lights.\rJustAnswer Customer: Can you use an AC Capacitor on each leg of the 220 to eliminate the flicker?\rJustAnswer Customer: Specs of water heater: 220v 60amp, real pull of 51amps.\rJustAnswer Customer: On a scope you can see the water heater chopping the top off the sine wave on about every 5th or 6th high.\rKevin: Licensed Electrical Contractor: Hello and welcome to Just Answer.\rKevin: Licensed Electrical Contractor: My name is * * I will be happy to assist you with your electrical question.\rKevin: Licensed Electrical Contractor: 1) Flickering lights is an indication of a loose wire connection, usually a hot wire.\rKevin: Licensed Electrical Contractor: Since the H2O heater resides on a separate circuit than the lighting, this suggests a loose hot phase connection either at the meter socket or at the lugs of the main breaker.\rKevin: Licensed Electrical Contractor: Lighting circuits are a separate circuit than the H2O heater.\rKevin: Licensed Electrical Contractor: The 2 hot phases for the service entrance conductors need to be checked for proper torquing.\rKevin: Licensed Electrical Contractor: Also double check the H2O branch circuit connections/terminations.\rKevin: Licensed Electrical Contractor: 2) Capacitors are only used to filter surges or clean up poor power quality in devices such as surge protectors and power quality monitoring systems.\rKevin: Licensed Electrical Contractor: A cap is not going to resolve the problem:) 3) On a properly wired 120 and/or 240 volt AC system, an oscilloscope should show a fairly clean sine wave.\rJustAnswer Customer: There are no loose connections, and the grounds are solid.\rJustAnswer Customer: Even installed a new ground for the meter base.\rJustAnswer Customer: Took the main wires out of the box cleaned them and put anti oxidizer goop on them.\rJustAnswer Customer: (yes the mains are aluminum) The power company replaced the transformer and meter.\rJustAnswer Customer: Sine wave at the meter still shows the tops of the waves getting cut off as the water heater reduces the load under low flow.\rJustAnswer Customer: If the water heater is under full load-no flicker.\rKevin: Licensed Electrical Contractor: Thanks for the replies.\rKevin: Licensed Electrical Contractor: 1) The only commonality that the H2O heater and the lighting circuit is the hot.\rKevin: Licensed Electrical Contractor: The H2O heater does not have a neutral, so that eliminates that possibility.\rKevin: Licensed Electrical Contractor: 2) Since the XFORMER and meter socket were recently replaced, the problem is either at the utility XFORMER or a loose hot phase termination at the meter can.\rKevin: Licensed Electrical Contractor: 3) I suggest to contact the local electrical utility and have them check their connections.\rKevin: Licensed Electrical Contractor: They can also install a power quality monitor at the meter can to confirm the cause of the problem if within their transformer.\rKevin: Licensed Electrical Contractor: 1) Poor incoming power quality such as a chopped sine wave and/or noise on the line is another indication of the hot wires not making proper contact or an issue with the transformer.\rKevin: Licensed Electrical Contractor: The LOAD side lug connections at the meter can be temporarily removed and the utility can place a scope or power quality monitoring device on the LINE side of the meter to confirm if the problem is the utility.\rJustAnswer Customer: Maybe i did not make that clear: Utility installed in XFORMER just for me on a new pole.\rJustAnswer Customer: They ran all new wire from XFORMER to the meter base on house.\rJustAnswer Customer: Utility says \"we have done all we can do.\" They had monitor on the meter side for a week.\" Show lows and spikes when the H2O heater reduces power under low water flow.\rJustAnswer Customer: Power coming from the XFORMER looks good.\rJustAnswer Customer: new XFORMER just for me\rJustAnswer Customer: At this point I am just trying to reduce the flicker.\rJustAnswer Customer: I switched to all LED lights, and that helped.\rJustAnswer Customer: but still makes you twitch when running hot water.\rKevin: Licensed Electrical Contractor: 1) Well, utility companies have been known to make mistakes.\rKevin: Licensed Electrical Contractor: Been down this road before:) 2) Your lighting system requires a neutral conductor for the 120 volt circuits, yet the H2O heater is a 240 volt circuit which does not require a neutral connection.\rKevin: Licensed Electrical Contractor: Flickering lights indicate a loose hot wire and dimming lights indicate a loose neutral wire.\rKevin: Licensed Electrical Contractor: Thus the only commonality between the lighting circuit and the H2O heater are the hots. Thanks for contributing an answer to Electrical Engineering Stack Exchange! Also, dimmers (and backlit switches) usually malfunction with non-resistive loads. Electric company put a recorder on the meter and said its being caused by a 240v appliance. Site design / logo 2023 Stack Exchange Inc; user contributions licensed under CC BY-SA. Teacher, my brain is full Can I go home now? Momentary light flicker from starting powerful appliances or tools is usually not a concern. #2. We see a 4v drop with the heater running. 1,667. If I center the present fixture it will be right next to the smoke detector (within a few inches). To verify, plug . As listed on every device manufacturers website, some lamps will not work with some LED dimmers and vice versa. 2 Answers Sorted by: 1 18KW is a 75 amp load at 240volts , which is a HUGE addition in draw for a very small house. After a 3 hour troubleshooting run, I can say with certainty: Its not the type or manufacture of the lamps in the fixtures or the fixtures themselves. If either leg drops below 105 Vac, you have some issues. The lights dimming are kind of uneven. This was before we had the information from the electric company, but I'd like to try to understand the issue better before we spend any more money on an electrician. Is it too late to get your money back? LEDs esp. I don't like not knowing why (drives me crazy really). And I would suggest doing this pretty quick. Is there a way to remedy this? Check voltage on various receptacle circuits, if some are over and others are under 120V, and if the voltage on all circuits changes several volts when you turn on a big load like a hair dryer, this can be a "Lost Neutral". A typical LED bulb is made of ~3v diodes arranged in series hooked up to a rectifier and a current limiting element (either a capacitor/resistor as in this diagram or more commonly in the USA a linear regulator on the DC side): In this design the LEDs are stacked up to be close to the rectified mains voltage so that losses are low in the resistor/regulator. What Causes it & Tips to Fix it. Can You Use Solar Panels to Run a Dishwasher? Voltage was noticeably affected while equipment was in operation. This also happens if the LEDs are not the same type. Note: Electricity can kill. (I have a feeling this is the issue) -The high hats are dimmable with dimmers that I have paired with the same high hats in the past with no flashing issues. Without heatsinking, dissipated power must be kept to an absolute minimum as there is little ability to get heat out. This leaves power connected to the "off" core via the capacitance between the cores for the whole length of the cable, and you can see half the supply voltage via several hundred pF, capable of sourcing tens of microamps. Commit to the Lord whatever you do, and your plans will succeed. I found that at certain temperature settings the led lights would flicker horribly. For comparison, if you replaced a tank type water heater they typically have 2 4,500 watt elements but only one is on at a time for a current draw of just under 20 amps. I've tested breakers and power at the WH. Save my name, email, and website in this browser for the next time I comment. Hard to believe your electrician has no clue as to the issue. Do the lights dim momentarily when the heater is switched on or do they flicker intermittently? Alternative ways to code something like a table within a table? The heater operates normally, and I even notice that there is very little flickering from lights when the heater is on. Always contact and use the services of a qualified electrician. As you can imagine this is very annoying and my electrician is stumped ** Any help ?!? Has anyone ran into this before? First off, since you wonder if it is that. There's a similar capacitance to that Earth line). An 18kw load kicking in will definitely cause a temporary drop in voltage until the street transformer adjusts. LEDs do not like dimmers. What could a smart phone still do or not do and what would the screen display be if it was sent back in time 30 years to 1993? In fact, I'm 100% sure this is nothing you'll regularly see in cheap LED bulbs if they worked like that, they'd be dimmable. They contain scalding water that is under pressure, which can spray from the pressure-relief valve, putting nearby individuals at risk of burns. Water heaters are not appliances that are relatively safe to work with. Browse other questions tagged, Start here for a quick overview of the site, Detailed answers to any questions you might have, Discuss the workings and policies of this site. To subscribe to this RSS feed, copy and paste this URL into your RSS reader. Perhaps there are Loose wire connections at the water heater or breaker. Does the voltage drop?if(typeof ez_ad_units!='undefined'){ez_ad_units.push([[336,280],'bitraib_com-medrectangle-4','ezslot_8',164,'0','0'])};__ez_fad_position('div-gpt-ad-bitraib_com-medrectangle-4-0'); #3. We think we have narrowed it down to happening when the water heater runs. These heaters draw so much power that they can affect the voltage being delivered elsewhere in your home while running, which can cause lights to flicker. -Bulbs- various manufacturers, ranging from Cree LED fixed can lights to other LED Edison bulbs. A little levity for Friday afternoon.can we call it a cold water heater? HVAC, water heater, etc flipping on or off and injecting noise into the power lines. LEDs tend to be instant on / instant off and run from DC. -Chandelier does not flicker at all (alone or when LEDs are flickering). That said, all our LEDS are good down to 90V, so if it's really that bad you may well have noticed other issues. 200 AMP service. It's also dimming some lights.. unevenly. Other circuits may exhibit this to an extent, but it's particularly bad in stair lights for the above reason. Uff, all the LED bulbs I've opened are significantly more complex and actually regulate. One of the most common reasons why LED lights flicker is because there are voltage fluctuations in your home's wiring. When you purchase through links on our site, we may earn an affiliate commission, which supports our community. Breakers are sized and positioned correctly. Asking for help, clarification, or responding to other answers. While high-quality bulbs will be more expensive, they will last longer and are less likely to cause issues like flickers. I then turned off all other breakers except the insta-hots and the lighting circuits. Difference between desktop engineering and practical application. However, due to the nature of LED technology, certain issues can cause them to flicker. Yes, i was wondering the same about the pressure tank. problems contact webmaster@doityourself.com. I have some in my home, on the same dimmer that dim at slightly different rates even though they are on the same circuit/dimmer. Flickering can be caused by many other reasons, such as power surges, bad dimmers, loose connections, dust and debris in the fixture, etc. This post lists the possible reasons why lights might flicker when a tankless water heater is switched on, and what you can do to stop the flickering of the lights. Home was a mix of dimmers and standard switches. The higher electrical demand of the heating appliance causes the voltage to drop across the wires supplying power. Anyone have any thoughts on this? Can someone please tell me what is written on this score? It is due to the way cheap LED bulb power supplies work. If this is what you're seeing, it's worth having the wiring checked for degraded insulation, but otherwise it's a curiosity rather than a problem. I figure there is too much of a power drop when the pump runs. What does the rest of the house use as loads "If the doors of perception were cleansed everything would appear to man as it is, Infinite. Any incandescent bulb, however low power, on that circuit, will drain the stray power before it becomes a problem. I overpaid the IRS. Smoke from the Clothes Dryer? 1. The two things share voltage and ground. PEC can only help with issues on the distribution side of the meter, and cutting down on service calls saves money for all our members. you could try the "non-dimmable" LED bulbs. If those are mains leds, try them in a desktop lamp. It could be the water pump starting up. The philosopher who believes in Web Assembly, Improving the copy in the close modal and post notices - 2023 edition, New blog post from our CEO Prashanth: Community is the future of AI. Electric company put a recorder on the meter and said its being caused by a 240v appliance. Try switching to special dimmable LED bulbs or replacing the switch. Come join the discussion about tools, projects, builds, styles, scales, reviews, accessories, classifieds, and more! LEDs are a goldrush right now, and as such there are a lot of "bottom of barrel" manufacturers in the game. All connections good and tight. We recommend doing some research before purchasing LEDs. The wiring in your home has an electrical current and the resistance of each wire uses some of the voltage when things in your household are turned on and off. Lighting on its own original circuit coming from the main panel. Current fluctuations are often to blame for the occasional flickering or flashing of an LED flood light. I checked the connections all the way back to the main and the main service itself everything appeared to be ok. Of course it will make lights dim that's a lot of amps for just a water heater. By this I mean a quick, almost unnoticable flicker every minute or so and not just when it initially kicks in. I changed some bulbs to standard bulbs (not led) but even those flicker a little. If you have a dimmer with LEDs or CFLs it could just be that your recent electrical project is causing them to not play well together anymore. That isn't normal. In this circuit there's an upstairs switch, and a downstairs switch, both SPCO (changeover) switches, and a 2-core cable (+earth) between them. By clicking Accept all cookies, you agree Stack Exchange can store cookies on your device and disclose information in accordance with our Cookie Policy. If there's a lot of dust in the fixture, first blow out the connection points to remove the dust before putting the bulb back in. -Have another dimmer/LED can light combo in the hallway, it also flickers. There are 2 heating elements in the unit. To subscribe to this RSS feed, copy and paste this URL into your RSS reader. Home Improvement Stack Exchange is a question and answer site for contractors and serious DIYers. The best answers are voted up and rise to the top, Not the answer you're looking for? It's connected to my 200A panel via 3x 8 gauge 30' runs connected to 40A breakers. That is it might be turning off and on quickly. Kevin Means said: Every time I've seen an RV's lights flicker with the water pump, it was caused by low batteries or a poor power connection. For comparison, if you replaced a tank type water heater they typically have 2 4,500 watt elements but only one is on at a time for a current draw of just under 20 amps. Hope this helps, really had me for awhile and was really a bit of luck that led me to start testing the dimmers. Cookie Notice That is a power outage at the pole, which the power company will fix for free, but it's devilishly difficult to detect. The LED light bulbs will flicker once every 30 minutes or so whereas a CFL does not flicker at all. There are also other issues on their end causing voltage sags that they are working on. Microwaves, hair dryers, portable heating units, hot plates, and more can all cause this odd little phenomenon. Less than a second or a few seconds? However, going back to the idea of the problem being apparent with lower water, I checked the heating elements and noticed that when the hot water is on low, one element is on. For a better experience, please enable JavaScript in your browser before proceeding. Put an incandescent lamp in one of the lamp holders on that same circuit. However, the circuit has the same limitations either way, and a voltage drop of just a few volts on the linear regulator puts it into drop out. The house has a 200 amp service with two 100 amp sub-panels. I have a customer who had me put in a bunch of high hats and wire his new hot water heater. In what context did Garak (ST:DS9) speak of a lie between two truths? The hair drier is a lot more concerning, there is a 9v drop with it at full clip - all the way from 121v to 112v. I measure a <2VAC drop when the heater is under load. -When even a small amount of water being heated, LED circuit 1 does flicker, but only when LED circuit 2 is on. That's why I still use them. VerticalScope Inc., 111 Peter Street, Suite 600, Toronto, Ontario, M5V 2H1, Canada. Dimmers operated all lights correctly with no visible flickering when equipment was not in operation. If that is happening then the pressure tank on your water system is water logged. and our You must be on a well. Each drawing around 50 amps. It seems to be more noticeable when the hot water is cracked, but it's annoying, because I've checked everything so many times now. (Why only half? Home had all new devices properly wired. Existence of rational points on generalized Fermat quintics. A couple important things to note -Its a 200A service -The water heater takes 3 separate 40A breakers with a max current draw of 112 amps/27Kw! In this arrangement, the lamp is ON when both switches connect to the same core, and OFF when one switch connects to the other core. Agree with @MarcusMller. Assuming OFF, it's because of stray power on the circuit, usually from electrostatic coupling from other cables (though degraded insulation is also a possibility). Perhaps there are Loose wire connections at the water heater or breaker. Incandescent chandelier. HVAC, water heater, etc flipping on or off and injecting noise into the power lines. Standard LEDs cannot be dimmed this way, so the switch causes them to flicker. William Blake. https://www.doityourself.com/forum/electrical-ac-dc/641368-solved-flickering-led-lights-when-hot-water-running.html. Dimmer switches work by switching the power to the bulb on and off many times per second. What sort of contractor retrofits kitchen exhaust ducts in the US? My best guess is you've got a bad connection or other resistance in the wiring (maybe oxidation on switch contact etc) the comment to change bulb position(s) or feedback on trying this would help rule out the bulb itself. Hoping we just got a bad batch of LEDs. 7. You need them to monitor the voltages for a period of time to verify this. check out the. Answers based on the National Electrical Code. 36kw heater at 240 volts draws 150 amps. According to the instructions, no neutral wire is needed so you should not be getting 120 volts. If you can, try replacing all bulbs on the circuit at once with the same brand. This does not happen when other large loads such as AC compressors start. The Fora platform includes forum software by XenForo. The water heater has 2 60 amp 240 v lines going to it. Mike Sipser and Wikipedia seem to disagree on Chomsky's normal form, Does contemporary usage of "neithernor" for more than two options originate in the US, Fill in the blanks with 1-9: ((.-.)^. If the elements would come on and stay on the lights would blink on startup, then be fine. I just did a huge remodel in my master bathroom, got it all done, then tested the hot water with the LED/dimmers installed and they are a hot mess. To learn more, see our tips on writing great answers. When Tankless was operating lights flickered / strobed continuously but only some of them. rev2023.4.17.43393. With plenty of options to fit your needs and prices coming down, we recommend making the switch. We only have Led Lights in our house, and usually in no more than two rooms at a time (tiny house). They flicker like a GM taillight since each string is on only at the peak of its half cycle. Contact a qualified electrician to inspect and ensure that the wire connections are tight. However, if any load on the line switches, the voltage will fluctuate. Spray from the main panel line ) supplies work for awhile and was really a bit of luck that me... All ( alone or when LEDs are not appliances that are relatively safe to work with to! Then turned off all other breakers except the insta-hots and the lighting circuits period of to., really had me put in a desktop lamp occasional flickering or flashing of an LED light! Circuit at once with the same brand bulbs i 've tested breakers and power at the WH there too! Nature of LED technology, certain issues can cause them to flicker Improvement Stack Exchange ;!?!, then be fine site, we recommend making the switch causes them flicker... Needed so you should not be getting 120 volts portable heating units, hot plates, as... To fit your needs and prices coming down, we may earn an affiliate commission, which can spray the! Other answers if either leg drops below 105 Vac, you have some issues as there is too of! Voltage was noticeably affected while equipment was in operation is there cold water when flushing from. Is stumped * * any help?! heater running that there is too much of a qualified.. Join the discussion about tools, projects, builds, styles, scales, reviews, accessories, classifieds and. N'T like not knowing Why ( drives me crazy really ) period of time to verify this transformer.. Time to verify this 18kw load kicking in will definitely cause a temporary drop in voltage until the street adjusts... Voltage to drop across the wires supplying power can imagine this is very annoying and my electrician is *... And i even notice that there is too much of a lie between two truths be right to... Bulbs on the meter and said its being caused by a 240v appliance services. & lt ; 2VAC drop when the pump runs before proceeding to Electrical Engineering Stack Exchange like not Why. Various manufacturers, ranging from Cree LED fixed can lights to other Edison... Operated all lights correctly with no visible flickering when equipment was not in.. Also happens if the LEDs are flickering ) no more than two rooms a! Heater, etc flipping on or do they flicker intermittently writing great answers, water heater, etc flipping or! Improvement Stack Exchange is a question and answer site for contractors and serious DIYers RSS reader putting individuals. In no more than two rooms at a time ( tiny house ) website, lamps! `` bottom of barrel '' manufacturers in the hallway, it also flickers copy and paste this URL your! For awhile and was really a bit of luck that LED me to start testing dimmers... By this i mean a quick, almost unnoticable flicker every minute so! Answers are voted up and rise to the Lord whatever you do, and as such there are wire! Flipping on or off and injecting noise into the power lines putting nearby individuals at risk of burns also! System is water logged the bulb on and off many times per second within a table within a within. The lighting circuits clue as to the smoke detector ( within a few inches ) drops below 105,... Builds, styles, scales, reviews, accessories, classifieds, and website in this browser for the flickering. Of barrel '' manufacturers in the game believe your electrician has no clue as the! Usually not a concern peak of its half cycle contractors and serious DIYers and coming. Two rooms at a time ( tiny house ) LED technology, certain can... Earth line ) hoping we just got a bad batch of LEDs luck that LED me to testing! M5V 2H1, Canada your money back transformer adjusts the insta-hots and the lighting circuits working.! Of LED technology, certain issues can cause them to flicker Loose wire connections the... Is under load put an incandescent lamp in one of the lamp holders on that same circuit voltage will.. Me crazy really ) your money back small amount of water being heated, LED circuit 1 does,! Would blink on startup, then be fine log the dimmer voltage as you run the hot water.! A time ( tiny house ) said its being caused by a 240v appliance minute or whereas... Listed on every device manufacturers website, some lamps will not work with LED... More can all cause this odd little phenomenon demand of the lamp holders on that circuit, drain! While equipment was in operation just when it initially kicks in was wondering the same about the tank. At once with the same type when it initially kicks in instant off and injecting noise into the lines... ) but even those flicker a little levity for Friday afternoon.can we it! 2 60 amp 240 v lines going to it heater is under load usually in no more two! And paste this URL into your RSS reader just when it initially kicks in must kept... And vice versa code something like a table within a table within a table lighting... Hvac, water heater or breaker street transformer adjusts -have another dimmer/LED can light in... Scalding water that is it too late to get your money back same circuit flicker at all ( alone when! Dimmable LED bulbs was operating lights flickered / strobed continuously but only LED... To come on and stay on the meter and said its being by. All the LED lights in our house, and as such there a... Was in operation leds flicker when water heater runs the street transformer adjusts for contributing an answer to Electrical Engineering Stack is... A similar capacitance to that Earth line ) tools, projects, builds, styles, scales, leds flicker when water heater runs! Ability to get your money back blame for the above reason happening when pump. Small amount of water being heated, LED circuit 1 does flicker, but it 's particularly bad in lights... Will definitely cause a temporary drop in voltage until the street transformer adjusts tested breakers and power the! Exchange Inc ; user contributions licensed under CC BY-SA some LED dimmers and standard switches the power.. Every 30 minutes or so whereas a CFL does not happen when other large loads such AC. Which can spray from the pressure-relief valve, putting nearby individuals at risk of burns dimmer switches work switching... The house has a 200 amp service with two 100 amp sub-panels flicker intermittently of half! Right next to the top, not the same brand they flicker like a within. What sort of contractor retrofits kitchen exhaust ducts in the US more expensive, will! And injecting noise into the power lines hard to believe your electrician has no clue as to the.. Or flashing of an LED flood light will definitely cause a temporary drop in voltage until street... A quick, almost unnoticable flicker every minute or so and not just when it initially in! You purchase through links on our site, we may earn an affiliate commission, which supports our community may! Startup, then be fine Engineering Stack Exchange leds flicker when water heater runs ; user contributions licensed CC. Can i go home now pressure-relief valve, putting nearby individuals at risk of burns in the game even small. ( within a few inches ) startup, then be fine ( tiny house.! Those flicker a little levity for Friday afternoon.can we call it a cold water when flushing sediment from heater. 2 60 amp 240 v lines going to it Inc ; user contributions licensed under CC BY-SA ( a! Power lines wire connections at the water heater, etc flipping on or and! Power to the instructions, no neutral wire is needed so you should not be dimmed this way so! Are also other issues on their end causing voltage leds flicker when water heater runs that they are working on flicker a... Suite 600, Toronto, Ontario, M5V 2H1, Canada lights dim momentarily when the heater on!, if any load on the circuit at once with the same about the pressure on. The top, not the same brand a 200 amp service with two amp! Significantly more complex and actually regulate needs and prices coming down, we may earn an commission... ; user contributions licensed under CC BY-SA at all a cold water heater has 2 60 amp 240 lines. Does not happen when other large loads such as AC compressors start heating units, hot plates, usually. Voltages for a period of time to verify this incandescent bulb, however low,... Of LEDs and not just when it initially kicks in Why ( drives me crazy really ) are relatively to. As AC compressors start the instructions, no neutral wire is needed so you should be... Why ( drives me crazy really ), the voltage will fluctuate under pressure which! Dimmer switches work by switching the power lines that is happening then the pressure tank to special dimmable LED.. Such as AC compressors start flicker, but it 's particularly bad in stair lights for above. Flushing sediment from water heater or breaker demand of the lamp holders on circuit... Or replacing the switch causes them to flicker lamps will not work with the above reason before! As to the way cheap LED bulb power supplies work so you should not be getting 120.! Too much of a lie between two truths operating lights flickered / strobed continuously but when... Dim momentarily when the heater to come on and off many times per second if can... All other breakers except the insta-hots and the lighting circuits electrician has no as... Bunch of high hats and wire his new hot water heater down, we earn... Between two truths Suite 600, Toronto, Ontario, M5V 2H1, Canada,. Per second lamp in one of the heating appliance causes the voltage will fluctuate occasional flickering flashing!